1-866-4 JJSTECH(1-866-455-7832)

GfG 4000 Series Integrated Controller, 1 Channel, 2 Amp Power Supply - 4100

Item #:
4100
Brand:
GfG
GfG 4000 Series Integrated Controller, 1 Channel, 2 Amp Power Supply - 4100
$1,105.00
Qty
Send This Page to a Friend

Ask an Expert

Our tech experts are ready to help!

1-866-4 JJSTECH (1-866-455-7832)

Email Us
Share this product:
GfG 4000 Series Integrated Controller, 1 Channel, 2 Amp Power Supply - 4100

GfG 4000 Series Integrated Controller, 1 Channel, 2 Amp Power Supply - 4100

$1,105.00

4100 4000 Series Integrated Controller, 1 Channel, 2 Amp Power Supply by GfG

The 4100 one-channel and the 4-channel 4400 gas warning systems offer safe and reliable gas detection

Alarm points

Each alarm can be adjusted separately. False alarms are eliminated with the adjustable alarm delay. The alarm point values can be freely adjusted within the detection range of the transmitter. Every alarm point value can be selected to be latching / non-latching or resettable / non resettable.

Alarm relays

The controller provides four voltage-free relays for the three alarms in addition to one fault warning. The relays may be used to control additional alarm devices like lights or horns. They can even prompt specific counter measures to prevent or limit dangers from gases or vapors.

Additional features

The 4100 control panel stores peak values and offers an additional 4-20 mA output. The 4400 control panel offers the ability to connect up to 4 transmitters and comes standard with an additional 24 VAC output for solenoid control.

Features

  • Complete 1-to-4 channel controller / gas monitoring system
  • 110 VAC or 24 VAC
  • Case-mounted horn / strobe
  • Security lock
  • Slim-line design
Gases Depending on transmitter:
Combustible / explosive
Toxic gases and vapors
Oxygen
Detection Range Depending on requirements: % LEL, % volume, ppm
Temperature range -4 to +122°F / -20 to +50°C
Power Supply Integrated 24 VDC
CULUSA
Input Signal 4-20 mA
Output Signal 1 output for each GMA 41
Alarms 3 adjustable alarm points
1 fault alarm
Alarm functions Exceeding / descending
Latching / non-latching
Resettable / non-resettable
Hysteresis adjustable
Delay-time 0 to 2 minutes
Alarm thresholds completely adjustable
Alarm allocation (4400)
Relay Outputs 4 voltage-free relays for alarm and fault
Normally closed contact (NC)
Normally open contact (NO)
Load: 250 VAC, 4A
Display 3-digit LED display
1 LED green - operational status
1 LED yellow - fault
3 LED red - alarm
Function keys Push-button operation for functions, like alarm points, calibration, function test and relay test
Models 4100 - 1 channel
4100-2 - 2 channels
*4100-3 - 3 channels
*4100-4 - 4 channels
4400 - 4 channels
4400-2 - 8 channels
*4400-3 - 12 channels
*4400-4 - 16 channels
4000-1400 - 5 channels
*4000-1140 - 6 channels
*4000-1114 - 7 channels
*4000-1440 - 9 channels
*4000-1144 - 10 channels
*4000-1444 - 13 channels
Power supply module 4100 - 24 VDC
4400 - 24 VDC / 24 VAC
Weight 14 pounds (64 g)
Dimensions 12x12x3.5 inches (305x305x89 mm) (HxWxD)
Optional Accessories
Alarm reset switch
ATEX Certificate (GMA 41) II (2) G BVS 03 ATEX G 005 X
Warranty Three years from date of purchase

Questions & Answers


There are no questions or answers for this item.